SO Pulse Output with Variable Constant
SO output for active kWh with configurable pulse constant (default 1000).
DEM4B403-1 is a 3P DIN-rail, direct-connected three-phase energy meter rated up to 80 A with Class 1.0 (Class B) accuracy. It supports RS485 communication with Modbus RTU and DL/T 645-2007 compatibility, SO pulse output with variable pulse constant and power outage display. MID B+D certified by SGS UK.
MID

SO output for active kWh with configurable pulse constant (default 1000).
Class 1.0 (Class B) active-energy measurement in accordance with EN 50470-3 and IEC 62053-21.
RS485 communication with Modbus RTU and DL/T 645-2007 protocols. Baud rate configurable from 9600 to 115200 bps.
Supports 4 metering modes: Forward only, Reverse only, Forward + Reverse (default), and Forward − Reverse.
MID B+D certified, confirming accuracy and quality for sub-billing applications across the EU.
Internal battery supports power outage display, keeping energy readings visible during power interruptions.
Solutions for AC/DC charging, billing and charging platform integration.
Explore ApplicationDC/PV monitoring for inverters, storage systems and distributed energy monitoring.
Explore ApplicationBranch metering for buildings, factories, tenants and energy allocation.
Explore ApplicationRack, cabinet and distribution power monitoring for data center operations.
Explore Application| Voltage connection | Direct connection |
| Rated voltage | 3 × 230/400 V |
| Frequency | 50/60 Hz |
| Current connection | Direct connection |
| Rated current | 0.25–5(80) A |
| Start current | 0.4% (20 mA) |
| Power consumption | ≤2 W / 10 VA |
| Pulse constant | 1000 imp/kWh |
| Active energy accuracy | Class 1.0 / Class B (IEC 62053-21) |
| Communication interface | RS485 |
| Protocol | Modbus RTU and DL/T 645-2007 |
| Communication type | Bidirectional |
| RS485 configuration | Baud rate: 9600 / 19200 / 38400 / 115200 bps |
| LCD display | 6+2 (7+1), scrolling display; voltage, current, energy, power, frequency |
| Power outage display | Supported via internal battery |
| LCD backlight | Yes |
| LED indicator | Impulse indication for active energy |
| Operating temperature | −25°C to +70°C |
| Relative humidity | ≤95% |
| Altitude | ≤2000 m |
| IP rating | IP51 indoor |
| Protection class | Class II (double or reinforced insulation) |
| UC class | UC2 |
| Wiring configuration | Three-phase four-wire (3P4W) |
| Applicable standards | EN 50470-3:2022 / EN IEC 62052-11:2021/A11:2022 / IEC 62052-31:2015 |