Modular Communication Architecture
Pluggable GPRS/4G, Ethernet, HPLC/RF or G3 PLC communication modules; uplink and downlink configurable per project requirements.
J52C002 is a modular smart data concentrator unit (DCU) built on a 32-bit Arm Cortex-A7 Linux platform for global AMI applications. It collects meter data, stores it locally and transfers it to the HES system. Features pluggable communication modules (G3 PLC), management of ≥300 meters, remote O&M, and firmware upgrade. Supports G3 PLC downlink communication.
Pluggable GPRS/4G, Ethernet, HPLC/RF or G3 PLC communication modules; uplink and downlink configurable per project requirements.
Each DCU manages at least 300 meter archives, including serial number, model and communication parameters.
G3 PLC downlink communication for meter reading and control, supporting automatic meter registration and network topology management.
Supports HES remote configuration, real-time reading, periodic reading, alarm push and DCU/meter firmware upgrade.
Remote firmware upgrade for both DCU and meters (DLMS image transfer), plus local USB upgrade.
Auto-detects new meters, tracks online status and retrieves network topology in real time.
| Wiring | 3-wire |
| Rated voltage | 3 × 230/400 V |
| Rated current | 5(10) A |
| Energy accuracy | Active: Class 0.5 (Class C); Reactive: Class 2 (Class A) |
| Pulse output | 6400 imp/kWh; 6400 imp/kvarh |
| Voltage range | 70%–130% Un |
| Frequency | 50 Hz |
| Standby power consumption | ≤8 W / 12 VA |
| Communication power consumption | ≤12 W / 15 VA |
| CPU | NXP Cortex®-A7 / i.MX6ULL (32-bit ARM) |
| SDRAM | 256 MB |
| Flash | 256 MB |
| Operating system | Linux (real-time embedded) |
| Internet protocol | IPv4 |
| Uplink ports | GPRS/4G, Ethernet |
| Downlink ports | HPLC/RF or G3 PLC |
| Local ports | 1 × RS232, 1 × USB, 1 × IR |
| Uplink communication | GPRS/4G, Ethernet |
| Downlink communication | G3 PLC |
| HES connection | TCP client with heartbeat keep-alive and automatic reconnection |
| Meter connection | G3 PLC module, 2 × RS485 ports |
| Local maintenance | USB, RS232, Ethernet Web, IR |
| Display | 160×160 dot-matrix LCD; LED indicators for operation, alarm, RS485-1/RS485-2 |
| Remote configuration | HES configures meter parameters via DCU (clock, tariff, threshold); remote relay control |
| Real-time reading | On-demand reading of meter status and instantaneous data; automatic retry up to 3 times |
| Periodic reading | Load profile, monthly billing, instantaneous curve, meter time sync; configurable interval (15 min / 1 h / 1 day / 1 month) |
| Alarm push | Monitors meter alarms and pushes to HES |
| Meter archive | Auto-detects new meters, pushes to HES, tracks online status and network topology |
| Data storage | Periodic meter data storage; 300 meters × 7 days load profile (typical) |
| Logging | Operation logs and communication records |
| Operating temperature | −25°C to +85°C (normal); −40°C to +85°C (limit) |
| Relative humidity | ≤95%, non-condensing |
| IP rating | IP51; IP54 with enclosure |
| Insulation class | Class II |
| Clock accuracy | ≤0.5 s/day |
| MTBF | ≥50,000 hours |
| Applicable standards | DLMS/COSEM (Green Book, Yellow Book, OBIS, IEC 62056) |
J52C002 is a smart data concentrator unit (DCU) for AMI, collecting meter data, storing it locally and transferring it to HES via G3 PLC downlink.
At least 300 meter archives per DCU, with local storage of 300 meters × 7 days load profile (typical).
Uplink: GPRS/4G and Ethernet. Downlink: G3 PLC and 2 × RS485. Local: RS232, USB, IR and Ethernet Web.
Yes. Remote DCU firmware upgrade and remote meter firmware upgrade via DCU (DLMS image transfer), plus local USB upgrade.
Linux on a 32-bit Arm Cortex-A7 (NXP i.MX6ULL) platform with 256 MB SDRAM and 256 MB Flash.
Tell us your requirements and our team will provide a professional solution and quotation within 24 hours.