≤75 ms Communication Refresh
Specified RS485 communication refresh time of ≤75 ms for applications requiring timely meter-side data updates.
DEM1E202 is a single-phase, direct-connected DIN-rail energy meter for 1P2W systems, with a maximum current of 45 A. It supports RS485 communication with Modbus RTU and DL/T 645-2007 compatibility, a specified RS485 communication refresh time of ≤75 ms, externally switched dual-tariff operation and multiple import/export energy calculation modes. The model is MID B+D certified by SGS UK.
MID

Specified RS485 communication refresh time of ≤75 ms for applications requiring timely meter-side data updates.
Class 0.5 active-energy and Class 1 reactive-energy measurement in accordance with IEC 62053-21.
RS485 communication compatible with Modbus RTU and DL/T 645-2007 protocols, with configurable baud rates from 9.6 to 115.2 kbps and addresses from 1 to 247.
Supports forward, reverse, absolute-value, algebraic-sum and net-energy calculation modes for flexible submetering applications.
Measures voltage, current, energy, power and power factor. EEP self-diagnostics and configurable monitoring alarms for kW, A, V, PF, kvar and kVA.
Supports external switching between two tariffs by default. DEM1E202 does not include an internal battery, RTC or time-scheduled TOU function.
Solutions for AC/DC charging, billing and charging platform integration.
Explore ApplicationDC/PV monitoring for inverters, storage systems and distributed energy monitoring.
Explore ApplicationBranch metering for buildings, factories, tenants and energy allocation.
Explore ApplicationRack, cabinet and distribution power monitoring for data center operations.
Explore Application| Wiring system | Direct connection, 1P2W |
| Rated voltage | 120-230V |
| Voltage tolerance | 0.8 to 1.15 Un |
| Frequency | 50/60Hz |
| Basic current (Ib) | 5A |
| Minimum current (Imin) | 0.15 A (MID) / 0.25 A (IEC) |
| Maximum current (Imax) | 45 A |
| Pulse constant | 1000 imp/kWh |
| Power consumption | ≤2 W / 10 VA |
| Rated impulse withstand voltage | 6 kV |
| Voltage accuracy | ±0.5% |
| Current accuracy | ±0.5% |
| Frequency accuracy | ±0.5% |
| Active power accuracy | ±0.5% |
| Reactive power accuracy | ±1% |
| Active energy accuracy | Class 0.5 |
| Reactive energy accuracy | Class 1 |
| Communication interface | RS485 |
| Communication direction | Bidirectional |
| Protocols | Modbus RTU; DL/T 645-2007 |
| Modbus address | 1–247 |
| Baud rate | 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbps |
| Parity | None / Odd / Even |
| Communication refresh time | ≤75 ms |
| Display | Backlit LCD with automatic display cycling |
| Default display cycle | 5 seconds |
| LCD refresh time | 500 ms |
| LED | Red pulse LED |
| Buttons | Page turning and setting |
| Ingress protection | IP20 |
| Overvoltage category | OVC III |
| Protection class | Class II |
| Installation | 1P DIN rail |
| Operating temperature | -40°C to +70°C |
| Storage / transport temperature | -40°C to +70°C |
| Reference temperature | 25 ± 2°C |
| Relative humidity | ≤95%, non-condensing |
| Altitude | ≤2,000 m |
| Housing dimensions | 18 mm × 94 mm × 62.4 mm |
| Applicable standards | IEC 62052-11:2020 / IEC 62053-21:2020 / IEC 62053-24:2020 / EN 50470-3:2022 |
DEM1E202 supports RS485 communication with Modbus RTU and DL/T 645-2007 compatibility. Confirm the required register list, baud rate and system settings before project deployment.
The current product specification lists a communication refresh time of ≤75 ms for the RS485 communication function. Actual end-to-end system performance also depends on controller polling, network configuration and system architecture.
No. DEM1E202 is an RS485 communication version. The SO pulse-output version in this series is DEM1E001.
No. DEM1E202 has no internal battery, RTC or TOU schedule. It supports two-rate tariff switching.
Yes. The meter supports multiple energy-calculation modes, including forward and reverse energy measurement, absolute-value calculation and algebraic energy calculation.
DEM1E202 is a direct-connected single-phase meter rated up to 45 A.
It can be evaluated for AC-side solar PV, BESS, AC EV charging, building submetering and industrial energy-monitoring applications. Confirm wiring, current, communication and market requirements before selection.
Submit your project requirements and target market. Our team will confirm the applicable document version and provide the appropriate technical materials.
Official DEM1E series datasheet covering product overview, specifications, wiring and dimensions.
Download DatasheetTell us your requirements and our team will provide a professional solution and quotation within 24 hours.