≤50 ms Power-Direction Data Refresh
Monitors power magnitude and direction with ≤50 ms data refresh for inverter/EMS-based zero-export or export-limit control in residential PV-storage, C&I and balcony PV systems.
M60313-9194 is a single-module (18 mm) DIN-rail, three-phase anti-reverse-flow energy meter with external split-core Rogowski coil sampling ranging from 200 A to 2400 A. It features ≤50 ms communication refresh time for real-time power direction monitoring, RS485 (Modbus RTU) and WiFi/Bluetooth wireless (MQTT) connectivity. Designed for C&I distributed PV, energy storage and EV charging applications requiring zero-export or export-limit control with inverter or EMS. Class 1 (Class B) accuracy. Designed in accordance with MID requirements.
Monitors power magnitude and direction with ≤50 ms data refresh for inverter/EMS-based zero-export or export-limit control in residential PV-storage, C&I and balcony PV systems.
Provides Class 1 (Class B) active-energy measurement for submetering and zero-export monitoring applications.
RS485 supports Modbus RTU at configurable 9.6–115.2 kbps rates. WiFi supports MQTT cloud connectivity; Bluetooth provides local wireless access.
Enables quick retrofit without interrupting the primary circuit, with selectable current ranges from 200 A to 2400 A.
Supports import, export, absolute value and algebraic sum metering, with alarms for voltage, current, phase and frequency abnormalities.
Supports selectable 200–2400 A Rogowski coil ranges for high-current PV, energy storage and C&I zero-export monitoring.
Solutions for AC/DC charging, billing and charging platform integration.
Explore ApplicationDC/PV monitoring for inverters, storage systems and distributed energy monitoring.
Explore ApplicationBranch metering for buildings, factories, tenants and energy allocation.
Explore ApplicationRack, cabinet and distribution power monitoring for data center operations.
Explore Application| Voltage connection | Direct voltage sampling |
| Rated voltage | 3 × 230/400 V |
| Voltage tolerance | 0.8 to 1.15 Un |
| Frequency | 50/60 Hz |
| Current connection | External split-core Rogowski coil |
| Current rating options | 100/200/400/600/800/1200/2400 A |
| Basic current (Ib) | 5–40 A |
| Minimum current (Imin) | 0.25–2 A |
| Maximum current (Imax) | 100–2400 A |
| Power consumption | ≤2 W / 10 VA |
| Pulse constant | 1000 imp/kWh, 1000 imp/kvarh |
| Voltage accuracy | ±1 % |
| Current accuracy | ±1 % |
| Frequency accuracy | ±1 % |
| Active power accuracy | ±1 % |
| Reactive power accuracy | ±2 % |
| Active energy accuracy | Class 1 (Class B) — IEC 62053-23 |
| Reactive energy accuracy | Class 2 (Class A) |
| Communication interface | RS485 + WiFi / Bluetooth |
| RS485 protocol | Modbus RTU |
| Wireless protocol | MQTT |
| Communication type | Bidirectional |
| RS485 configuration | Modbus address: 1 to 247; baud rate: 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbps; parity: None / Odd / Even |
| Specified communication refresh time | ≤50 ms |
| LCD display | 6+2 energy display; automatic cyclic display with white backlight; 500 ms refresh |
| LED indicators | Pulse indicator; communication indicator |
| Buttons | Page turning and setting |
| Metering function | Monitors energy consumption and key electrical variables: current, voltage, active/reactive power, power factor and frequency |
| Metering mode | Absolute value, algebraic sum, import, export and separate import/export |
| Anti-reverse-flow application | Real-time power magnitude and direction output to inverter or EMS for zero-export or export-limit control |
| Event alarms | Undervoltage, overcurrent/overload, overvoltage, phase loss, frequency deviation and phase sequence error; backlight flashing alarm |
| Firmware upgrade | Local upgrade and remote upgrade |
| Other functions | Voltage, RS485 and CT wiring all use pluggable connections; consecutive register addressing for easy system integration |
| Operating temperature | −40°C to +70°C |
| Relative humidity | ≤95%, non-condensing |
| Altitude | ≤2000 m |
| IP rating | IP30; install in an IP54 outdoor or IP51 indoor enclosure |
| Overvoltage category | OVC III |
| Protection class | Class II |
| Rated impulse withstand voltage | 6 kV |
| Installation method | 35 mm DIN-rail mounting, single module (18 mm) |
| Applicable standards | IEC 62052-11:2021+A11:2022 / IEC 62053-23:2020 / EN 50470-3:2022 |
M60313-9194 is a single-module (18 mm) DIN-rail, three-phase anti-reverse-flow energy meter with external split-core Rogowski coil sampling ranging from 200 A to 2400 A. It features ≤50 ms communication refresh time for real-time power direction monitoring, RS485 (Modbus RTU) and WiFi/Bluetooth wireless (MQTT) connectivity. Designed for C&I distributed PV, energy storage and EV charging applications requiring zero-export or export-limit control with inverter or EMS. Class 1 (Class B) accuracy. Designed in accordance with MID requirements.
The meter monitors power magnitude and direction in real time (≤50 ms refresh) and works with an inverter or EMS to achieve zero-export or export-limit control for distributed PV and storage applications.
External split-core Rogowski coil, supporting 200–2400 A with flexible installation. No primary circuit interruption required.
RS485 supports Modbus RTU. WiFi/Bluetooth supports MQTT for cloud connectivity.
WiFi and Bluetooth with MQTT protocol for cloud connectivity.
Absolute value, algebraic sum, import, export and separate import/export metering for flexible energy management.
Designed in accordance with MID requirements (certification pending). Complies with IEC 62052-11:2021+A11:2022, IEC 62053-23:2020 and EN 50470-3:2022.
Tell us your requirements and our team will provide a professional solution and quotation within 24 hours.