Class 0.5S Active Energy Accuracy
Class 0.5S (IEC 62053-22) active-energy measurement with ±0.2 % voltage and current accuracy supports high-precision power monitoring for distribution applications.
YTL72-320D is a 72 mm panel-mount multifunction digital power meter with dot-matrix LCD display. It supports CT input at 5(6) A, three-phase high-accuracy measurement (Class 0.5S), dual communication architecture (RS485 + Y-Bus), 4 digital inputs, 2 digital outputs, SOE event records and 10-type event alarms. Y-Bus enables external sensor connectivity for temperature and humidity monitoring.
Class 0.5S (IEC 62053-22) active-energy measurement with ±0.2 % voltage and current accuracy supports high-precision power monitoring for distribution applications.
RS485 communication compatible with Modbus RTU and DL/T 645-2007 protocols. Default 115200 bps, 2-wire connection, supports up to 64 devices. Communication response time ≤100 ms.
Y-Bus interface supports up to 5 downstream sensors for temperature and humidity monitoring. Default 9600 bps, Modbus protocol. Enables comprehensive environmental and electrical monitoring in a single device.
4 dry-contact digital inputs with built-in power supply (response < 300 ms) and 2 digital outputs (NO contacts, AC 250 V/5 A). SOE event records with millisecond timestamps capture electrical parameters when DI/DO is triggered.
Supports alarms for current imbalance, overcurrent, overload, overvoltage, undervoltage, low battery, voltage imbalance, phase-sequence error, low power factor and voltage/current circuit faults.
72 × 72 mm panel-mount frame with 66 × 66 mm cutout. Dot-matrix LCD with white backlight. Panel IP54, operating temperature −40°C to +70°C.
Solutions for AC/DC charging, billing and charging platform integration.
Explore ApplicationDC/PV monitoring for inverters, storage systems and distributed energy monitoring.
Explore ApplicationBranch metering for buildings, factories, tenants and energy allocation.
Explore ApplicationRack, cabinet and distribution power monitoring for data center operations.
Explore Application| Voltage connection | Direct / PT |
| Rated voltage | AC 3×57.7/100 V, AC 3×63.5/110 V, AC 3×230/400 V |
| Voltage tolerance | 0.8 to 1.15 Un |
| Current connection | CT |
| Basic current (Ib) | 5 A |
| Minimum current (Imin) | 0.05 A |
| Maximum current (Imax) | 6 A |
| Operating frequency | 50 Hz / 60 Hz |
| Meter constant | 10000 imp/kWh, 10000 imp/kvarh |
| Auxiliary power supply | AC 85–276 V, DC 95–350 V |
| Power consumption | ≤1 VA per phase; auxiliary ≤2 W, ≤10 VA |
| Voltage accuracy | ±0.2 % |
| Current accuracy | ±0.2 % |
| Frequency accuracy | ±0.02 Hz |
| Active power accuracy | ±0.5 % |
| Reactive power accuracy | ±2 % |
| Active energy accuracy | Class 0.5S (IEC 62053-22) |
| Reactive energy accuracy | Class 2 |
| Voltage / current harmonic accuracy | ±1 % |
| Communication interface | RS485 + Y-Bus |
| Y-Bus communication | Y-Bus proprietary protocol for external sensor connectivity |
| Y-Bus configuration | Default: 9600 bps, 8 data bits, 1 stop bit, no parity; supports up to 5 downstream sensors |
| Protocol | RS485 compatible with Modbus RTU and DL/T 645-2007; Y-Bus supports Modbus protocol |
| Communication type | Bidirectional |
| RS485 configuration | Default: 115200 bps, 8 data bits, 2 stop bits, no parity; 2-wire; max. 64 connections |
| Communication response time | ≤100 ms |
| LCD display | Dot-matrix LCD (D), white backlight; menu key, left key, right key, confirm key |
| Metering function | Full parameter measurement: voltage, current, energy, power, power factor and demand |
| Metering mode | Absolute-value, algebraic-sum and separate import/export metering |
| Digital inputs | 4 dry-contact inputs; built-in power supply; response time < 300 ms |
| Digital outputs | 2 digital outputs; normally open contacts; AC 250 V / 5 A, DC 30 V / 5 A |
| SOE records | SOE event records with millisecond timestamps; records electrical parameters when DI/DO is triggered |
| Event alarms | Current imbalance, overcurrent, overload, overvoltage, undervoltage, low battery, voltage imbalance, phase-sequence error, low power factor, voltage/current circuit fault |
| Firmware upgrade | Local upgrade |
| Panel IP rating | IP54 |
| Housing IP rating | IP20 |
| Protection class | Class II |
| Wiring method | 3P4W, compatible with 3P3W (ARON) |
| Altitude | < 2000 m |
| Impulse withstand voltage | 6 kV |
| Frame size | 72 × 72 mm |
| Housing dimensions | 65.3 × 65.3 × 80.5 mm |
| Cutout dimensions | 66 × 66 mm |
| Applicable standards | GB/T 17215.211:2021 / GB/T 17215.321:2021 / IEC 62052-11:2020 / IEC 62053-22:2020 / IEC 61557-12:2021 |
What is YTL72-320D?
YTL72 series uses a 72×72 mm frame (cutout 66×66 mm). YTL96 series uses a 96×96 mm frame (cutout 86×86 mm). The 96 frame also supports AC 3×400/690 V rated voltage.
RS485 supports Modbus RTU and DL/T 645-2007 protocols with a response time of ≤100 ms.
Y-Bus is a proprietary communication protocol developed by YTL, supporting up to 5 downstream sensors for temperature and humidity monitoring. Default 9600 bps, Modbus protocol.
4 dry-contact digital inputs (response < 300 ms) and 2 digital outputs (NO contacts, AC 250 V/5 A, DC 30 V/5 A). SOE event records with millisecond timestamps capture electrical parameters.
Official YTL-72 series datasheet covering product overview, specifications, wiring and dimensions.