Class 0.5S Active Energy Accuracy
Class 0.5S (IEC 62053-22) active-energy measurement with ±0.2 % voltage and current accuracy supports high-precision power monitoring for distribution applications.
YTL96-223D is a 96 mm panel-mount multifunction digital power meter with dot-matrix LCD display. It supports CT input at 5(6) A, three-phase high-accuracy measurement (Class 0.5S), dual communication architecture (RS485 + Y-Bus), 2nd–63rd harmonic analysis, 4 digital inputs, 2 digital outputs, SOE event records and 10-type event alarms. It also supports AC 3×400/690 V rated voltage.
Class 0.5S (IEC 62053-22) active-energy measurement with ±0.2 % voltage and current accuracy supports high-precision power monitoring for distribution applications.
RS485 communication compatible with Modbus RTU and DL/T 645-2007 protocols. Default 115200 bps, 2-wire connection, supports up to 64 devices. Communication response time ≤100 ms.
Supports 2nd to 63rd voltage harmonics and 2nd to 63rd current harmonics with ±1 % accuracy for professional power quality monitoring in HV/LV distribution systems.
Y-Bus proprietary protocol developed by YTL supports up to 5 downstream sensors for temperature and humidity monitoring. Default 9600 bps, Modbus protocol.
4 dry-contact digital inputs (response < 300 ms) and 2 digital outputs (NO contacts, AC 250 V/5 A). SOE event records with millisecond timestamps and 10-type event alarms.
96 × 96 mm panel-mount frame with 86 × 86 mm cutout. Supports AC 3×400/690 V rated voltage. Dot-matrix LCD with white backlight. Panel IP54, operating temperature −40°C to +70°C.
Solutions for AC/DC charging, billing and charging platform integration.
Explore ApplicationDC/PV monitoring for inverters, storage systems and distributed energy monitoring.
Explore ApplicationBranch metering for buildings, factories, tenants and energy allocation.
Explore ApplicationRack, cabinet and distribution power monitoring for data center operations.
Explore Application
YTL96-223D is a 96 mm panel-mount multifunction digital power meter with dot-matrix LCD display. It supports CT input at 5(6) A, three-phase high-accuracy measurement (Class 0.5S), dual communication architecture (RS485 + Y-Bus), 2nd–63rd harmonic analysis, 4 digital inputs, 2 digital outputs, SOE event records and 10-type event alarms. It also supports AC 3×400/690 V rated voltage.
YTL72 series uses a 72×72 mm frame (cutout 66×66 mm). YTL96 series uses a 96×96 mm frame (cutout 86×86 mm). The 96 frame also supports AC 3×400/690 V rated voltage.
RS485 supports Modbus RTU and DL/T 645-2007 protocols with a response time of ≤100 ms.
Y-Bus is a proprietary communication protocol developed by YTL, supporting up to 5 downstream sensors for temperature and humidity monitoring. Default 9600 bps, Modbus protocol.
4 dry-contact digital inputs (response < 300 ms) and 2 digital outputs (NO contacts, AC 250 V/5 A, DC 30 V/5 A). SOE event records with millisecond timestamps capture electrical parameters.
2nd to 63rd voltage harmonics and 2nd to 63rd current harmonics with ±1 % accuracy for power quality monitoring.
Official YTL-96 series datasheet covering product overview, specifications, wiring and dimensions.
Download PDFTell us your requirements and our team will provide a professional solution and quotation within 24 hours.