Advanced Multi-Parameter Metering
Measures 70+ electrical parameters including energy, power, voltage, current, frequency, power factor and demand, with 4-quadrant import/export analysis.
DEM4K103 is a 3P DIN-rail, CT-operated three-phase energy meter rated at 5(6) A with Class C accuracy. It supports RS485 communication with Modbus RTU and DL/T 645-2007 protocols, RTC-based 4-tariff metering and flexible CT/PT ratio configuration (up to 1000:1). Includes internal battery for RTC timekeeping. MID B+D certified by SGS UK.
MID

Measures 70+ electrical parameters including energy, power, voltage, current, frequency, power factor and demand, with 4-quadrant import/export analysis.
Class C active-energy measurement in accordance with IEC 62053-21 and EN 50470-3.
Supports Modbus RTU and DL/T 645-2007 protocols, with configurable baud rates from 9600 to 115200 bps.
CT and VT ratios are configurable up to 1000:1 for different transformer-operated metering requirements.
Supports up to 4 tariffs with RTC-based timekeeping for time-of-use energy measurement and tariff switching.
Built-in battery and RTC support reliable clock retention and stable multi-tariff operation during power interruptions.
Solutions for AC/DC charging, billing and charging platform integration.
Explore ApplicationDC/PV monitoring for inverters, storage systems and distributed energy monitoring.
Explore ApplicationBranch metering for buildings, factories, tenants and energy allocation.
Explore ApplicationPower monitoring for factories, process energy analysis and equipment circuits.
Explore Application| Voltage connection | CT / PT |
| Rated voltage | 3 × 230/400 V; 3 × 400 V |
| Frequency | 50/60 Hz |
| Current connection | CT (external current transformer) |
| Rated current | 0.05–5(6) A |
| Start current | 5 mA |
| CT ratio | Up to 1000:1 |
| PT ratio | Up to 1000:1 |
| Power consumption | < 2 W / < 10 VA |
| Pulse constant | 10000 imp/kWh |
| Active energy accuracy | Class C (IEC 62053-21) |
| Communication interface | RS485 |
| Protocol | Modbus RTU and DL/T 645-2007 |
| Communication type | Bidirectional |
| RS485 configuration | Baud rate: 9600 / 19200 / 38400 / 115200 bps |
| LCD display | 6+2 (7+1), auto decimal point shift, blue backlight; 2 buttons for paging and setting |
| Metering function | Measures active/reactive energy, active/reactive power, voltage, current, frequency, power factor, demand and apparent power |
| Metering mode | 1. Total = Forward; 2. Total = Reverse; 3. Total = Forward + Reverse (default); 4. Total = Forward − Reverse |
| Tariff function | 4 tariffs with RTC scheduling |
| CT/PT ratio | CT ratio 1–1000:1; PT ratio 1–1000:1; configurable via RS485/IR and buttons |
| LED indicator | Impulse indication |
| Operating temperature | −40°C to +70°C |
| Average humidity | ≤75% (non-condensing) |
| Maximum humidity | ≤95% |
| Altitude | ≤2000 m |
| IP rating | IP51 indoor |
| Protection class | Class II |
| UC class | UC1 |
| Wiring configuration | Three-phase four-wire (3P4W) and three-phase three-wire (3P3W) |
| Applicable standards | IEC 62053-21:2020 / EN 50470-3:2022 / EN IEC 62052-11:2021/A11:2022 / IEC 62052-31:2024 |
What is DEM4K103?
CT operated with external current transformers. Supports 3P4W and 3P3W (Aron) wiring.
RS485 with Modbus RTU and DL/T 645-2007 protocols.
RTC-based 4-tariff metering with time scheduling. For a model without tariff functions, see DEM4K003.
CT ratio up to 1000:1 and PT ratio up to 1000:1, configurable via communication interface and buttons.
MID B+D certified by SGS UK.
Official DEM4K series datasheet covering product overview, specifications, wiring and dimensions.