Class 0.5S Active Energy Accuracy
Class 0.5S (IEC 62053-22) active-energy measurement with ±0.2 % voltage and current accuracy supports high-precision power monitoring for distribution applications.
YTL96-202D is a 96 mm panel-mount multifunction digital power meter with dot-matrix LCD display. It supports CT input at 5(6) A, three-phase high-accuracy measurement (Class 0.5S), RS485 communication, 2nd–63rd voltage and current harmonic analysis and 10-type event alarms. It also supports AC 3×400/690 V rated voltage for HV/LV distribution monitoring.
Class 0.5S (IEC 62053-22) active-energy measurement with ±0.2 % voltage and current accuracy supports high-precision power monitoring for distribution applications.
RS485 communication compatible with Modbus RTU and DL/T 645-2007 protocols. Default 115200 bps, 2-wire connection, supports up to 64 devices. Communication response time ≤100 ms.
Supports 2nd to 63rd voltage harmonics and 2nd to 63rd current harmonics with ±1 % accuracy for professional power quality monitoring in HV/LV distribution systems.
Measures voltage, current, energy, active/reactive power, power factor, frequency and demand. Supports absolute-value, algebraic-sum and separate import/export metering modes.
Supports alarms for current imbalance, overcurrent, overload, overvoltage, undervoltage, low battery, voltage imbalance, phase-sequence error, low power factor and voltage/current circuit faults.
96 × 96 mm panel-mount frame with 86 × 86 mm cutout. Supports AC 3×400/690 V rated voltage. Dot-matrix LCD with white backlight. Panel IP54, operating temperature −40°C to +70°C.
Solutions for AC/DC charging, billing and charging platform integration.
Explore ApplicationDC/PV monitoring for inverters, storage systems and distributed energy monitoring.
Explore ApplicationBranch metering for buildings, factories, tenants and energy allocation.
Explore ApplicationRack, cabinet and distribution power monitoring for data center operations.
Explore Application| Voltage connection | Direct / PT |
| Rated voltage | AC 3×57.7/100 V, AC 3×63.5/110 V, AC 3×230/400 V |
| Rated voltage (96 frame) | Also supports AC 3×400/690 V |
| Voltage tolerance | 0.8 to 1.15 Un |
| Current connection | CT |
| Basic current (Ib) | 5 A |
| Minimum current (Imin) | 0.05 A |
| Maximum current (Imax) | 6 A |
| Operating frequency | 50 Hz / 60 Hz |
| Meter constant | 10000 imp/kWh, 10000 imp/kvarh |
| Auxiliary power supply | AC 85–276 V, DC 95–350 V |
| Power consumption | ≤1 VA per phase; auxiliary ≤2 W, ≤10 VA |
| Voltage accuracy | ±0.2 % |
| Current accuracy | ±0.2 % |
| Frequency accuracy | ±0.02 Hz |
| Active power accuracy | ±0.5 % |
| Reactive power accuracy | ±2 % |
| Active energy accuracy | Class 0.5S (IEC 62053-22) |
| Reactive energy accuracy | Class 2 |
| Voltage / current harmonic accuracy | ±1 % |
| Communication interface | RS485 |
| Protocol | RS485 compatible with Modbus RTU and DL/T 645-2007 |
| Communication type | Bidirectional |
| RS485 configuration | Default: 115200 bps, 8 data bits, 2 stop bits, no parity; 2-wire; max. 64 connections |
| Communication response time | ≤100 ms |
| LCD display | Dot-matrix LCD (D), white backlight; menu key, left key, right key, confirm key |
| Metering function | Full parameter measurement: voltage, current, energy, power, power factor, demand and harmonic content |
| Metering mode | Absolute-value, algebraic-sum and separate import/export metering |
| Harmonic analysis | 2nd to 63rd voltage and 2nd to 63rd current harmonics (±1 % accuracy) |
| Event alarms | Current imbalance, overcurrent, overload, overvoltage, undervoltage, low battery, voltage imbalance, phase-sequence error, low power factor, voltage/current circuit fault |
| Firmware upgrade | Local upgrade |
| Panel IP rating | IP54 |
| Housing IP rating | IP20 |
| Protection class | Class II |
| Wiring method | 3P4W, compatible with 3P3W (ARON) |
| Altitude | < 2000 m |
| Impulse withstand voltage | 8 kV between current circuit and ground; 8 kV between each unconnected terminal and ground; 8 kV between line and ground |
| Operating temperature | −40°C to +70°C |
| Frame size | 96 × 96 mm |
| Housing dimensions | 85.3 × 85.3 × 80.5 mm |
| Cutout dimensions | 86 × 86 mm |
| Applicable standards | GB/T 17215.211:2021 / GB/T 17215.321:2021 / IEC 62052-11:2020 / IEC 62053-22:2020 / IEC 61557-12:2021 |
YTL96-202D is a 96 mm panel-mount multifunction digital power meter with dot-matrix LCD display. It supports CT input at 5(6) A, three-phase high-accuracy measurement (Class 0.5S), RS485 communication, 2nd–63rd voltage and current harmonic analysis and 10-type event alarms. It also supports AC 3×400/690 V rated voltage for HV/LV distribution monitoring.
YTL72 series uses a 72×72 mm frame (cutout 66×66 mm). YTL96 series uses a 96×96 mm frame (cutout 86×86 mm). The 96 frame also supports AC 3×400/690 V rated voltage.
RS485 supports Modbus RTU and DL/T 645-2007 protocols with a response time of ≤100 ms.
2nd to 63rd voltage harmonics and 2nd to 63rd current harmonics with ±1 % accuracy for power quality monitoring.
−40°C to +70°C. Suitable for demanding distribution environments when panel-mounted in an appropriately rated enclosure.
Official YTL-96 series datasheet covering product overview, specifications, wiring and dimensions.
Download PDFTell us your requirements and our team will provide a professional solution and quotation within 24 hours.